Solar: 2571W - 38s | Charging from solar | Charge rate: 32A
Voltage: 0.003V | Available Current 857000A | Smoothed Current: 861164.8A
The max charge rate was set to 15A and the car was charging with 15A while it should have been charging with 11A.
The V topic is set correctly but it could have been that the link with the MQTT broker was lost for a while. In other words, if OpenEVSE would have a MQTT watchdog and would stop charging when the connection with the MQTT broker is lost, then this problem would probably not happen. A sanity check on the received value might also useful, ie. if V outside sensible range, then set V = 240 (default for EU).
The text was updated successfully, but these errors were encountered:
Hi.
Solar: 2571W - 38s | Charging from solar | Charge rate: 32A
Voltage: 0.003V | Available Current 857000A | Smoothed Current: 861164.8A
The max charge rate was set to 15A and the car was charging with 15A while it should have been charging with 11A.
The V topic is set correctly but it could have been that the link with the MQTT broker was lost for a while. In other words, if OpenEVSE would have a MQTT watchdog and would stop charging when the connection with the MQTT broker is lost, then this problem would probably not happen. A sanity check on the received value might also useful, ie. if V outside sensible range, then set V = 240 (default for EU).